NB1L Kaçak Akım Korumalı Otomatik Sigorta

Rated residual operating current I∆n ≤30 mA: additional protection in the case of direct contact. I∆n ≤300 mA: preventative fire protection in the case of ground fault currents. Tripping class AC class Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase. A class Tripping is ensured for sinusoidal, alternating residual currents as well as for pulsed DC residual currents, whether they be quickly applied or slowly increase. Tripping curve B curve (3-5 In) protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems. C curve (5-10 In) protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current. 

 